Introduction: Reading YT106 coil voltage and contact ratings correctly means treating the coil drive, the coil power group, and the contact limits as three separate decisions.
Choosing a YT106 coil voltage begins with separating the coil drive from the contact limits. Your control board rail is fixed, the load is small, and the relay data offers six coil voltages and three power groups. First select the coil your driver can actually energise. Then check the contacts against the load they will switch. These are two separate readings; combining them into one number can reject a workable candidate or approve one for the wrong job. A 24 VDC rail with a low-current load makes the order visible: coil current sets driver burden; contact rating sets the load path.
The coil is the input side: an electromagnet defined by nominal voltage, rated current, coil resistance and coil power. The contacts are the output side: they describe what the relay can switch after it operates. A 24 VDC coil and a 2 A contact rating can appear in the same part, but they answer different questions. Coil data follows the ordinary relationships among voltage, current, resistance and power, so the values can be checked directly. In the 0.15 W group, the 12 VDC option uses 960 Ω and 12.5 mA, which gives 0.15 W (12 V × 12.5 mA). The 24 VDC option uses 3,840 Ω and 6.3 mA and lands at the same power. Use that check to match the rail and estimate driver current. The coil data also lists a maximum allowable voltage for each coil. Use the nominal voltage for design, treat the maximum as a ceiling, and do not assume it is a recommended continuous operating voltage. The 24 VDC 0.20 W coil is listed at 8.3 mA and 2,880 Ω; that 2 mA difference matters when the driver is close to its source or sink limit. The contact rating does not help with that choice; it becomes relevant after the coil is energised.
The 150 mW figure is a highlighted option within the 0.15 W group, not a rating shared by every YT106. Its scope matters because low coil power can help when the board has a tight current budget, but the driver still has to supply the selected coil at the selected voltage. The YT106 technical data separates the coil range into three power groups: about 0.15 W, 0.20 W, and 0.36 W. Each group answers a different question about the driver.
Across the 0.15 W and 0.20 W groups, the same 24 VDC rail produces 6.3 mA or 8.3 mA, so the driver's output current and voltage drop set the practical choice. The 0.36 W group has no verified resistance column to support the same calculation, so it remains outside the current comparison. Ask for corrected 0.36 W data and the ordering code for the 150 mW option before finalising that path.
Contact data separates resistive load ratings from maximum switching limits. The resistive ratings are 1 A at 125 VAC and 2 A at 30 VDC. The contact data also lists a maximum switching current of 2 A, a maximum switching voltage of 125 VAC or 30 VDC, and a maximum switching power of 125 VA or 60 W. Each is a separate limit. A product of current and voltage is not a substitute for the listed power limit. 2 A × 125 VAC gives 250 VA, but the switching power limit is 125 VA. Separate current and voltage capability does not create a combined 2 A at 125 V rating. Check the load against current, voltage, and power separately. The published ratings describe resistive loads. A solenoid, small motor, or lamp can bring inrush or inductive kick that a resistive figure does not cover, so those loads need separate evaluation. Response times follow the same conditional reading: action time is a maximum of 6 ms at rated voltage, and release time is a maximum of 4 ms without a diode across the coil. Both are maximum values under stated conditions, not fixed delays for every circuit. As a design evaluation, suppose the control board runs a 24 VDC rail and switches a low-current signal load. First confirm the 24 VDC coil is available; it is listed in the 0.15 W and 0.20 W groups. Next compare the driver’s ability to supply 6.3 mA or 8.3 mA at that rail, depending on the group. Then compare the load voltage and current against the resistive ratings and against each maximum limit separately. A 0.1 A resistive load at 12 VDC sits inside all of those limits, so the next questions become footprint, wiring, and driver behaviour at coil turn-off.
Reading YT106 coil and contact data becomes simpler in two passes. On the coil side, select the voltage your board already provides, choose between the 0.15 W and 0.20 W groups based on available drive current, and hold the 0.36 W group until its figures are confirmed. On the contact side, keep the resistive ratings and the three maximum switching limits separate, then match the real load type and magnitude against each one. Once you have chosen a voltage and power group, send us the rail voltage, the load you intend to switch, and the power group you are considering. As a miniature power relay supplier, we can help you confirm the matching ordering code for the 150 mW option and the PCB layout drawing for your footprint check.
A: Start with the voltage your board already supplies. YT106 coil options are 3, 5, 6, 9, 12, and 24 VDC; a 24 VDC rail points to the 24 VDC coil and a 12 VDC rail to the 12 VDC coil, while other voltages matter with an adjustable regulator or separate coil supply. Once voltage is fixed, compare the 0.15 W and 0.20 W groups at that voltage because they require different drive current and coil resistance. The 24 VDC 0.15 W option is listed at 6.3 mA and the 24 VDC 0.20 W option at 8.3 mA, so check the driver's output current and voltage drop before sizing the circuit.
A: No. The 150 mW label does not cover all YT106 builds; it identifies one low-power choice inside the 0.15 W group. The coil table lists about 0.15 W, 0.20 W, and 0.36 W groups, and the ordering information lists 0.15 W as an optional choice. A relay built with a 0.20 W coil draws more current at the same nominal voltage than the 150 mW version, which changes the driver supply requirement. Ask for the complete ordering code for the 150 mW option so the part matches the coil you designed around.
A: Compare the load against each published limit as a separate check. The resistive ratings are 1 A at 125 VAC and 2 A at 30 VDC; maximum switching current is 2 A; maximum switching voltage is 125 VAC or 30 VDC; and maximum switching power is 125 VA or 60 W. The wattage figure stands as its own ceiling, so a current-voltage product cannot set the load limit. For example, 2 A at 125 VAC would calculate to 250 VA, which exceeds the 125 VA switching-power limit. Confirm the load is resistive, because inductive and lamp loads behave differently from the conditions these ratings describe.